Schneider Electric SpaceLogic C-Bus Home Controller command execution |
NAME
Schneider Electric SpaceLogic C-Bus Home Controller command execution
- Platforms Affected:
Schneider Electric SpaceLogic C-Bus Home Controller 5200WHC2 - Risk Level:
8.8 - Exploitability:
Proof of Concept - Consequences:
Gain Access
DESCRIPTION
Schneider Electric SpaceLogic C-Bus Home Controller could allow a remote authenticated attacker to execute arbitrary commands on the system, caused by OS command injection vulnerability in the delsnap.pl Perl/CGI script. By sending a specially-crafted request using the name GET parameter, an attacker could exploit this vulnerability to execute arbitrary commands as the root user on the system.
CVSS 3.0 Information
- Privileges Required: Low
- User Interaction: None
- Scope: Unchanged
- Access Vector: Network
- Access Complexity: Low
- Confidentiality Impact: High
- Integrity Impact: High
- Availability Impact: High
- Remediation Level: Unavailable
MITIGATION
No remedy available as of July 29, 2022.